Fuji Temp Controller - PXR4-RAY1-GV0A1

Alternate Part Number: PXF4ABY2-FVYA1

Quick Overview

Temp Controller, 1/16 DIN (48x48mm), 100-240VAC, Relay
$244.00

Standard Stock

- +

The Fuji PXR series (except for the PXR3) will be replaced by the new PXF series at the end of 2017. 

Our Fuji PXR temperature controllers have auto-tuning and fuzzy controls as well as self-tuning. Self-tuning automatically re-tunes the controller under certain conditions, without the need to revert to auto-tuning.

The screw-terminal on the back eliminates the need for a socket! 

Remote monitoring of up to 31 Fuji PXR temperature controllers at a time is possible with the RS485 option that uses the industry-standard Modbus ™ protocol. The communications option comes with our free Windows®-based software, PXR-LITE ™. The software allows you to program the Fuji PXR controller from the PC and view real-time data and trend graph while logging the data on to a text file.

Standard Features Include:

  • PID with auto-tuning, PID self-tuning and fuzzy control are installed as standard.
  • Front side waterproof specification in conformity with NEMA4X (standard).
  • Two alarms are equipped, and 8-step ramp/soak function can be installed as an option.
Additional Information
Part Number PXR4-RAY1-GV0A1
Product Series PXR4
Availability Please Contact Us
Product Series PXR Series
Digital or Analog Digital
Input Thermocouple (t/c) Only
Output Relay Output, Alarm
Size 1/16 DIN 48x48mm
Ratings NEMA 4X
Weight - lbs. 0.4410
Base Unit of Measure Each
Specification Tab

General Specifications

Power supply voltage

  • 100 V (-15%) to 240 V (+10%) AC, 50/60 Hz or 24 V (±10%) AC 50/60 Hz, 24 V (±10%) DC

Power consumption

  • When using 100 V AC: 8 VA or less
  • When using 220 V AC: 10 VA or less
  • When using 24 V AC/DC: 10VA

Insulation resistance

  • 20 MΩ or more (500 V DC)

Dielectric strength

  • Power supply-ground: 1500 V AC for 1 min
  • Power supply-others: 1500 V AC for 1 min
  • Ground-relay output: 1500 V AC for 1 min
  • Ground-alarm output: 1500 V AC for 1 min
  • Others: 500 V AC for 1 min

Input impedance

  • Thermocouple: 1 MΩ or more
  • Voltage: 450 kΩ or more
  • Current: 250Ω (external resistor)

Allowable signal source resistance

  • Thermocouple: 100Ω or less
  • Voltage: 1 kΩ or less
Resources

Need More Information?

General Specifications


Power supply voltage



  • 100 V (-15%) to 240 V (+10%) AC, 50/60 Hz or 24 V (±10%) AC 50/60 Hz, 24 V (±10%) DC


Power consumption



  • When using 100 V AC: 8 VA or less

  • When using 220 V AC: 10 VA or less

  • When using 24 V AC/DC: 10VA


Insulation resistance



  • 20 MΩ or more (500 V DC)


Dielectric strength



  • Power supply-ground: 1500 V AC for 1 min

  • Power supply-others: 1500 V AC for 1 min

  • Ground-relay output: 1500 V AC for 1 min

  • Ground-alarm output: 1500 V AC for 1 min

  • Others: 500 V AC for 1 min


Input impedance



  • Thermocouple: 1 MΩ or more

  • Voltage: 450 kΩ or more

  • Current: 250Ω (external resistor)


Allowable signal source resistance



  • Thermocouple: 100Ω or less

  • Voltage: 1 kΩ or less

Customer Reviews